delabs circuits
Electronic Engineering Schematics
RTD Pt-100 Four Point Alarm - del90001
Here 4052 is used as an analog multiplexer, U3A TL062 opamp is
wired as a 1mA Constant Current Source. It pumps 1mA into
U2 4052 pin 13 X . Depending on BCD code on
inputs A, B of 4052 the current is routed to any one of
the four RTD 100E, whose one end is connected to X0-X3. The
current then flows to GND thru the Platinum 100E resistance. The
Y0-Y3 monitors the mV developed on RTD in tandem with
X0-X3 positions. Like a ganged rotary
switch. The Output mV at Y is the mV of Active Channel as
selected by the BCD of 4029.
See another way 4052 is used to route analog signals to DPM -
Analog
mV Switch for Digital Meters
The BCD is provided by 4029 counter which is clocked by a 555.
U5A cancels out the 100E mV (1mA * 100E) of a cold RTD and
Amplifies the differential mV. This output of U5A is in
proportion with measured temperature. U5B compares the mV that
was obtained with a preset mV of POT1, which is a
user setting called setpoint. The difference is amplified by U5B
which is saturated by U3B comparator which adds a little
hysteresis too. R7-C2 further dampen and slow the response. This
finally drives Q2 to provide a Logic Signal indicating if
temperature is below or above setpoint.
To view the circuit below, Click the Link of PNG or PDF and
view the Circuit, PNG can be Scrolled with Drag-Drop
Left-Click-Mouse and you could use the PDF to take a paper
print for reference only.
PNG-Schematic
PDF-Circuit
RTD Pt-100 Four Point Alarm - del90001
Below is a Preview Image Linked to the Larger Circuit
It is important to understand process control theory and the
material technologies that go into these sensors too.
Here is a instrument i used to make in a similar need -
Multizone
Process Scanner
Four points in a Closed Loop Temperature Control System is
Monitored and a Alarm set to go off when the temperature goes
beyond the set limit.
Back to Design Service and
Projects
...
delabs Technologies
20th Mar 2020